induwara.lk
induwara.lkSri Lanka · Utility

Sri Lanka Cable Size Calculator — Wire Gauge & Amp Rating

Find the right copper or aluminium cable size for any load — in both mm² and the local strand code (7/0.67, 7/0.85…) your hardware shop uses. It sizes the breaker, derates for heat and grouping, and checks the 4% voltage drop over your run.

By Induwara AshinsanaUpdated Jul 18, 2026
Size your cable
IEC 60364 · Kelani V5
Popular

Only used when the load is entered as power (kW).

m

One-way distance from board to load.

°C

Use 35–40 for hot roof-space runs.

Cables bunched in the same conduit / tray.

%

CEB default is 4%.

Recommended cable
1.5 mm²7/0.53
Design current (Ib)
9.7 A
Breaker (MCB) In
10 A
Voltage drop
2.68%
6.2 V over the run
Earth (CPC)
1.5 mm²
IEC 60364-5-54

Motor / AC load: use a Type-C (or Type-D) MCB to ride through start-up inrush, and consider one size up for long runs and repeated starts.

Why this size — candidate comparison

SizeStrandDerated ADrop %Verdict
1 mm²1/1.1312.24.07%too much drop
1.5 mm²pick7/0.5315.52.68%OK
2.5 mm²7/0.6721.61.66%OK
4 mm²7/0.8528.21.02%OK
6 mm²7/1.0435.70.67%OK
10 mm²7/1.3548.90.41%OK
16 mm²7/1.7064.90.26%OK
25 mm²7/2.1484.60.16%OK
35 mm²7/2.52104.30.12%OK

Sources: Kelani Cables Catalogue V5 (strand codes & local ratings), IEC 60364-5-52 (ampacity, derating & mV/A/m), IEC 60364-5-54 (earth conductor), CEB / SLS 733 (4% drop limit). Guidance only — a PUCSL-licensed electrician must certify the installation.

How it works

This calculator follows the cable-selection procedure in IEC 60364-5-52, the wiring-systems standard that Sri Lanka's installation practice adopts, and reads its current ratings and strand codes from the Kelani Cables Catalogue V5. It works in five steps.

  1. Design current (Ib). For a single-phase load, Ib = P / (V × pf); for three-phase, Ib = P / (√3 × V × pf). Enter a current directly and it is used as-is. Appliance presets carry a typical power and power factor (motors ≈ 0.8, resistive heaters = 1.0).
  2. Protective device (In). The breaker is the smallest standard BS EN 60898 rating — 6, 10, 16, 20, 25, 32, 40, 50, 63 A — that is at least Ib, satisfying the IEC 60364-4-43 rule Ib ≤ In ≤ Iz.
  3. Required tabulated rating (It).The cable's table rating must clear the breaker after derating: It ≥ In / (Ca × Cg). Ca is the ambient-temperature factor (IEC Table B.52.14 — e.g. 0.94 at 35 °C, 0.87 at 40 °C for 70 °C PVC) and Cg is the grouping factor (Table B.52.17 — 1.0 for a single circuit, 0.80 for two bunched, and so on).
  4. Cable selection. The tool takes the smallest size whose method-specific rating — enclosed in conduit (B), clipped direct (C) or buried (D) — meets It. A 1.0 mm² conductor is treated as lighting-only, so power circuits start at 1.5 mm².
  5. Voltage-drop check. Vd = (mV/A/m × Ib × L) / 1000, and %Vd = Vd / V × 100. If the drop exceeds your limit (4% by default under CEB rules), the size steps up until it passes. Finally the earth conductor is sized by IEC 60364-5-54 Table 54.7: equal to the phase up to 16 mm², 16 mm² between 16 and 35 mm², and half the phase above that.

The mV/A/m figures are cross-checked against first principles using the conductor resistance R = ρ × L / A at operating temperature, which reproduces the catalogue values to within about 3% — confirmation the voltage-drop side is grounded in physics, not a lookup alone.

Worked examples

1.5-ton AC, 22 m in conduit

  1. Load: 2.0 kW, pf 0.9, single-phase 230 V
  2. Ib = 2000 / (230 × 0.9) = 9.66 A → breaker In = 10 A
  3. Ambient 35 °C → Ca = 0.94, so It ≥ 10 / 0.94 = 10.64 A
  4. 1.5 mm² (7/0.53) enclosed = 16.5 A ≥ 10.64 A ✓
  5. Voltage drop = 29 × 9.66 × 22 / 1000 = 6.16 V = 2.68% < 4% ✓
  6. Result: 1.5 mm² (7/0.53) — an existing 2.5 mm² run is more than enough.

40 A house main, 8 m tails in conduit

  1. Main rating In = 40 A, single-phase 230 V
  2. Ambient 35 °C → Ca = 0.94, so It ≥ 40 / 0.94 = 42.55 A
  3. 6 mm² (7/1.04) enclosed = 38 A ✗ (below 42.55 A)
  4. 10 mm² (7/1.35) enclosed = 52 A ≥ 42.55 A ✓
  5. Voltage drop = 4.4 × 40 × 8 / 1000 = 1.41 V = 0.61% < 4% ✓
  6. Result: 10 mm² (7/1.35) tails with a 10 mm² earth (CPC).

1-ton AC on a very long 120 m run (voltage-drop driven)

  1. Load: 1.4 kW, pf 0.9, single-phase 230 V → Ib = 6.76 A, In = 10 A
  2. Ampacity alone allows 1.5 mm² (16.5 A ≥ 10 A) ✓
  3. But drop on 1.5 mm² = 29 × 6.76 × 120 / 1000 = 23.5 V = 10.2% ✗
  4. 2.5 mm² → 6.35% ✗; step up again
  5. 4 mm² (7/0.85) → 11 × 6.76 × 120 / 1000 = 8.92 V = 3.88% < 4% ✓
  6. Result: 4 mm² (7/0.85) — the long run, not the current, sets the size.

Frequently asked questions

Sources & references

The ampacity, mV/A/m and derating tables on this page were last cross-checked against the Kelani Catalogue V5 and IEC 60364-5-52 on 2026-07-18. This tool covers 70 °C PVC copper (and basic aluminium) house wiring — AC final circuits and main tails. It is guidance only: a PUCSL-licensed electrician must design and certify the actual installation.

Related tools

Rate this tool
Be the first to rate

Comments & feedback

Spotted a bug or want an improvement? Tell us — our team reviews every comment, and good ideas get built. Comments are public and anonymous.

Found a bug, edge case, or want to suggest an improvement?

Email me at [email protected] — most fixes ship within 24 hours.